Automatic Cylinder Reciprocating System

The hydraulic circuit shown in Fig. 1.8 produces continuous reciprocation of a double-acting cylinder using two sequence valves. Each sequence valve senses the completion of stroke by the corresponding build-up pressure. Each check valve and the corresponding pilot line prevent the shifting of the four-way valve until the particular stroke of the cylinder is completed.

The check valves are needed to allow pilot oil to leave either end of the DCV while the pilot pressure is applied to the opposite end. This permits the spool of the DCV to shift as required.

01. June 2018 by Dan
Categories: Hydraulic Circuits | Leave a comment

Hydraulic Cylinder Sequencing Circuits

Hydraulic cylinders can be operated sequentially using a sequence valve. Figure 1.7 shows that two sequence valves are used to sequence the operation of two double-acting cylinders. When the DCV is actuated to its right-envelope mode, the bending cylinder (B) retracts fully and then the clamp cylinder (A) retracts.

This sequence of cylinder operation is controlled by sequence valves. This hydraulic circuit can be used in a production operation such as drilling. Cylinder A is used as a clamp cylinder and cylinder B as a drill cylinder. Cylinder A extendsand clamps a work piece. Then cylinder B extends to drive a spindle to drill a hole. Cylinder B retracts the drill spindle and then cylinder A retracts to release the work piece for removal.

01. June 2018 by Dan
Categories: Hydraulic Circuits | Leave a comment

Counterbalance Valve Application

A counterbalance valve (Fig. 1.6) is applied to create a back pressure or cushioning pressure on the underside of a vertically moving piston to prevent the suspended load from free falling because of gravity while it is still being lowered.

Valve Operation (Lowering)
The pressure setting on the counterbalance valve is set slightly higher than the pressure required to prevent the load from free falling. Due to this back pressure in line A, the actuator piston must force down when the load is being lowered. This causes the pressure in line A to increase, which raises the spring-opposed spool, thus providing a flow path to discharge the exhaust flow from line A to the DCV and then to the tank. The spring-controlled discharge orifice maintains back pressure in line A during the entire downward piston stroke.

Valve Operation (Lifting)
Asthe valve is normally closed, flow in the reverse direction (from port B to port A) cannot occur without a reverse free-flow check valve. When the load is raised again, the internal check valve opens to permit flow for the retraction of the actuator.

Valve Operation (Suspension)
When the valve is held in suspension, the valve remains closed. Therefore, its pressure setting must be slightly higher than the pressure caused by the load. Spool valves tend to leak internally under pressure. This makes it advisable to use a pilot-operated check valve in addition to the counterbalance valve if a load must be held in suspension for a prolonged time.

01. June 2018 by Dan
Categories: Hydraulic Circuits | Leave a comment

Control of a Single-Acting Hydraulic Cylinder

Figure 1.1 shows that the control of a single-acting,spring return cylinder using a three-way two-position manually actuated, spring offset direction-control valve (DCV). In the spring offset mode, full pump flow goes to the tank through the pressure-relief valve (PRV). The spring in the rod end of the cylinder retracts the piston as the oil from the blank end drains back into the tank. When the valve is manually actuated into its next position, pump flow extends the cylinder.

After full extension, pump flow goes through the relief valve. Deactivation of the DCV allows the cylinder to retract as the DCV shifts into its spring offset mode.

01. June 2018 by Dan
Categories: Hydraulic Circuits | Leave a comment

Bleed-Off Circuit

Compared to meter-in and meter-out circuits, a bleed-off circuit is less commonly used. Figure 1.10 shows a bleed-off circuit with extend stroke control. In this type of flow control, an additional line is run through a flow-control valve back to the tank. To slow down the actuator, some of the flow is bledoff through the flow-control valve into the tank before it reaches the actuator. This reduces the flow into the actuator, thereby reducing the speed of the extend stroke.

The main difference between a bleed-off circuit and a meter-in/meter-out circuit is that in a bleed-off circuit, opening the flow-control valve decreases the speed of the actuator, whereas in the case of a meter-in/meter-out circuit, it is the other way around.

01. June 2018 by Dan
Categories: Hydraulic Circuits | Leave a comment

Meter-Out Circuit

Figure 1.9 shows a meter-out circuit for flow control during the extend stroke. When the cylinder extends, the flow coming from the pump into the cylinder is not controlled directly. However, the flow out of the cylinder is controlled using the flow-control valve (metering orifice). On the other hand, when the cylinder retracts, the flow passes through the check valve unopposed, bypassing the needle valve. Thus, only the speed during the extend stroke is controlled.

Both the meter-in and meter-out circuits mentioned above perform the same operation (control the speed of the extending stroke of the piston), even though the processes are exactly opposite to one another.

01. June 2018 by Dan
Categories: Hydraulic Circuits | Leave a comment

Meter-In Circuit

Figure 1.8 shows a meter-in circuit with control of extend stroke. The inlet flow into the cylinder is controlled using a flow-control valve. In the return stroke, however, the fluid can bypass the needle valve and flow through the check valve and hence the return speed is not controlled. This implies that the extending speed of the cylinder is controlled whereas the retracing speed is not.

01. June 2018 by Dan
Categories: Hydraulic Circuits | Leave a comment

Pressure-Compensated Valves

Pressure-compensated flow-control valvesovercome the difficulty causedby non-pressure-compensated valves by changing the size of the orifice in relation to the changes in the system pressure. This is accomplished through a spring-loaded compensator spool that reduces the size of the orifice when pressure drop increases. Once the valve is set, the pressure compensator acts to keep the pressure drop nearly constant. It works on a kind of feedback mechanism from the outlet pressure. This keeps the flow through the orifice nearly constant.

Schematic diagram of a pressure compensated flow-control valve is shown in Fig. 1.5 and its graphical symbol in Fig. 1.6. A pressure-compensated flow-control valve consists of a main spool and a compensator spool. The adjustment knob controls the main spool’s position, which controls the orifice size at the outlet. The upstream pressure is delivered to the valve by the pilot line A. Similarly, the downstream pressure is ported to the right side of the compensator spool through the pilot line B. The compensator spring biases the spool so that it tends toward the fully open position. If the pressure drop across the valve increases, that is, the upstream pressure increases relative to the downstream pressure, the compensator spool moves to the right against the force of the spring. This reduces the flow that in turn reduces the pressure drop and tries to attain an equilibrium position as far as the flow is concerned.

In the static condition, the hydraulic forces hold the compensator spool in balance, but the bias spring forces it to the far right, thus holding the compensator orifice fully open. In the flow condition, any pressure drop less than the bias spring force does not affect the fully open compensator orifice,but any pressure drop greater than the bias spring force reduces the compensator orifice. Any change in pressure on either side of the control orifice, without a corresponding pressure change on the opposite side of the control orifice, moves the compensator spool. Thus, a fixed differential across the control orifice is maintained at all times. It blocks all flow in excess of the throttle setting. As a result, flow exceeding the preset amount can be used by other parts of the circuit or return to the tank via a pressure-relief valve.

Performance of flow-control valve is also affected by temperature changes which changes the viscosity of the fluid. Therefore, often flow-control valves have temperature compensation. Graphical symbol for pressure and temperature compensated flow-control valve is shown in Fig. 1.7.

01. June 2018 by Dan
Categories: Flow Control Valves | Leave a comment

Non-Pressure-Compensated Valves

Non-pressure-compensated flow-control valves are used when the system pressure is relatively constant and motoring speeds are not too critical. The operating principle behind these valves is that the flow through an orifice remains constant if the pressure drop across it remains the same. In other words, the rate of flow through an orifice depends on the pressure drop across it.

The disadvantage of these valves is discussed below. The inlet pressure is the pressure from the pump that remains constant. Therefore, the variation in pressure occurs at the outlet that is defined by the work load. This implies that the flow rate depends on the work load. Hence, the speed of the piston cannot be defined accurately using non-pressure-compensated flow-control valves when the working load varies. This is an extremely important problem to be addressed in hydraulic circuits where the load and pressure vary constantly.

Schematic diagram of non-pressure-compensated needle-type flow-control valve is shown in Fig. 1.3. It is the simplest type of flow-control valve. It consists of a screw (and needle) inside a tube-like structure. It has an adjustable orifice that can be used to reduce the flow in a circuit. The size of the orifice is adjusted by turning the adjustment screw that raises or lowers the needle. For a given opening position, a needle valve behaves as an orifice. Usually, charts are available that allow quick determination of the controlled flow rate for given valve settings and pressure drops.

Sometimes needle valves come with an integrated check valve for controlling the flow in one direction only. The check valve permits easy flow in the opposite direction without any restrictions. As shown in Fig. 1.4, only the flow from A to B is controlled using the needle. In the other direction (B to A), the check valve permits unrestricted fluid flow.

01. June 2018 by Dan
Categories: Flow Control Valves | Leave a comment

Pilot-Operated Unloading Valve

A pilot-operated unloading valve has less pressure override than its direct-acting counterpart.So it does not dump part of the flow prematurely.

A pilot-operated unloading relief valve is the same as a pilot-operated relief valve with the addition of an unloading spool. Without the unloading spool, this valve would function just like any pilot-operated relief valve. Pressure buildup in the pilot section would open some flow to the tank and unbalance the poppet, allowing it to open and relieve excess pump flow.

Schematic diagram of unloading valve is shown in Fig. 1.10.In a pilot-operated unloading valve; the unloading spool receives a signal through the remote-pilot port when pressure in the working circuit goes above its setting. At the same time, pressure on the spring-loaded ball in the pilot section starts to open it. Pressure drop on the front side of the unloading spool lowers back force and pilot pressure from the high-pressure circuit forces the spring-loaded ball completely off its seat. Now there is more flow going to the tank than what the control orifice can keep up with. The main poppet opens at approximately 20 psi. Now, all high-volume pump flow can go to the tank at little or no pressure drop and all horsepower can go to the low-volume pump to do the work. When pressure falls approximately 15% below the pressure set in the pilot section, the spring-loaded ball closes and pushes the unloading spool back for the next cycle.

An unloading valve requires no electric signals. This eliminates the need for extra persons when troubleshooting. These valves are very reliable and seldom require maintenance, adjustment or replacement.An unloading valve unloads the pump when the desired pressure is reached.It allows rapid discharge of pressurized oil near atmospheric pressure.As soon as the system pressure reaches the setting pressure that is available at the pilot port, it lifts the spool against the spring force.When the spool is held by the pilot pressure, the delivery from the pump goes to the tank.An unloading valve is used to perform operations such as stamping, coining, punching, piercing, etc.

Figure1.11shows the application of unloading valve in a punching press. It is a circuit that uses a high-pressure, low-flow pump in conjunction with a low-pressure, high-flow pump. In a punching press, the hydraulic cylinder must extend rapidly over a great distance with low-pressure, high-flow requirements. This rapid extension of cylinder occurs under no external load (when the punching tool approaches the sheet metal).But during punching operation for short motion, the pressure requirements are high due to punching load. During this cylinder travel, high-pressure, low-flow requirements are needed.

When punching operation begins, the increased pressure opens the unloading valve to unload the low-pressure pump. The purpose of relief is to protect the high-pressure pump from over pressure at the end of the cylinder stroke and when direction control valve (DCV) is in its spring centered mode. The check valve protects the low-pressure pump from high pressure, which occurs during punching operation that occurs at the end of cylinder extension and when the DCV is in its spring centered mode.

The above circuit given in Fig. 1.11 eliminates the necessity of having a very expensive high-pressure, high-flow pump.

01. June 2018 by Dan
Categories: Pressure Control Valves | Leave a comment

← Older posts

Newer posts →